Carrier Miraco Fan Coil Units in Egypt — Concealed Ducted FCU Range
Three series, 29 models with catalogue data, for consultants, contractors and procurement teams. Selection from the load schedule — proposals with an engineering check table and submittal. النسخة العربية: فان كويل للمشاريع
Short answer
El Shora Cooling Solutions (شركة الشورى لحلول التبريد والتكييف والتهوية) is an Egyptian HVAC contractor based in 6th of October City, founded in 2016. It supplies and installs Carrier Miraco chilled-water fan coil units (made in Egypt) for malls, hotels, hospitals and office buildings across Egypt: the 42MKT3 Aqua Slim range (24.3 cm high, 3-row coil, 50 Pa, 7/12 °C), the 42MKS4 district-cooling range (4-row coil rated at 5.5/14.5 °C), the 42MKT4 4-row range (7/12 °C, 30 Pa) and 100 Pa high-static models — 400 to 2,200 CFM. Units are selected from the load schedule, water temperatures and external static pressure, and every proposal carries an engineering check table and a submittal. No published prices — +20 2 3691 4695, WhatsApp +20 110 057 4656.
Content last reviewed: 3 November 2026
The three series — and the high-static models
| Series | Coil | External static | Rated water | Airflow range | Typical use |
|---|---|---|---|---|---|
| 42MKT3 Aqua Slim | 3 rows, 7 mm tubes (9.52 mm on 1200/1400) | 50 Pa | 7 / 12 °C | 400–1,400 CFM | Low ceilings: hotel rooms, offices, villas on chilled water — only 24.3 cm high |
| 42MKS4 District Cooling | 4 rows, 9.52 mm tubes | 30 Pa (400–600) / 50 Pa (600 Plus, 800–2,000) | 5.5 / 14.5 °C (ΔT 9 K) | 400–2,000 CFM | Mall shops and towers on district-cooling networks |
| 42MKT4 | 4 rows, 9.52 mm tubes | 30 Pa | 7 / 12 °C | 400–1,200 CFM | Higher loads per CFM, higher latent loads, short duct runs |
| 42MKT3H / 42MKT4H (G100) | 3 or 4 rows | 100 Pa | project water temperatures | 1,600–2,200 CFM nominal | Long duct runs, many outlets, extra filters — full datasheet sent with the proposal |
The units, from the catalogues

42MKT3 Aqua Slim — 3-row coil, 24.3 cm high

42MKS4 — 4-row coil rated at 5.5/14.5 °C

42MKT4 — 4-row coil at 7/12 °C
Full range — 29 models with catalogue data
Airflow in CFM at high/medium/low speed; cooling capacity in kW at medium speed (the speed normally used for selection); dimensions length × height × depth in cm.
| Model | Series | Rows | ESP (Pa) | Airflow CFM H/M/L | Cooling kW (medium) | Dimensions cm |
|---|---|---|---|---|---|---|
| 42MKT3(7)-400G50A | 42MKT3 slim (24.3 cm) | 3 | 50 | 425/266/168 | 2.83 | 90.8 × 24.3 × 48.2 |
| 42MKT3(7)-500G50A | 42MKT3 slim (24.3 cm) | 3 | 50 | 494/347/185 | 3.73 | 90.8 × 24.3 × 48.2 |
| 42MKT3(7)-600G50A | 42MKT3 slim (24.3 cm) | 3 | 50 | 625/403/230 | 4.21 | 100.3 × 24.3 × 48.2 |
| 42MKT3(7)-800G50A | 42MKT3 slim (24.3 cm) | 3 | 50 | 878/627/379 | 6.5 | 136.8 × 24.3 × 48.2 |
| 42MKT3(7)-1000G50A | 42MKT3 slim (24.3 cm) | 3 | 50 | 1012/879/674 | 8.06 | 136.8 × 24.3 × 48.2 |
| 42MKT3(9)-1200G50A | 42MKT3 slim (24.3 cm) | 3 | 50 | 1206/925/566 | 8.39 | 165.8 × 24.3 × 48.2 |
| 42MKT3(9)-1400G50A | 42MKT3 slim (24.3 cm) | 3 | 50 | 1367/1142/844 | 10.54 | 189.8 × 24.3 × 48.2 |
| 42MKS4-400G30 | 42MKS4 district cooling | 4 | 30 | 351/288/213 | 3.43 | 94.1 × 24.1 × 52.2 |
| 42MKS4-500G30 | 42MKS4 district cooling | 4 | 30 | 428/408/351 | 4.33 | 94.1 × 24.1 × 52.2 |
| 42MKS4-600G30 | 42MKS4 district cooling | 4 | 30 | 559/530/437 | 6.14 | 116.1 × 24.1 × 52.2 |
| 42MKS4-600G50-Plus | 42MKS4 district cooling Plus | 4 | 50 | 664/627/554 | 4.96 | 116.1 × 24.1 × 52.2 |
| 42MKS4-800G50-A4 | 42MKS4 district cooling | 4 | 50 | 748/718/656 | 6.69 | 118 × 34 × 61.2 |
| 42MKS4-1000G50-A4 | 42MKS4 district cooling | 4 | 50 | 856/821/773 | 7.33 | 118 × 34 × 61.2 |
| 42MKS4-1200G50-A4 | 42MKS4 district cooling | 4 | 50 | 1138/983/891 | 9.12 | 136.9 × 34 × 61.2 |
| 42MKS4-1400G50-A4 | 42MKS4 district cooling | 4 | 50 | 1284/1088/975 | 10.3 | 136.9 × 34 × 61.2 |
| 42MKS4-1600G50-A4 | 42MKS4 district cooling | 4 | 50 | 1412/1183/1078 | 10.72 | 136.9 × 34 × 61.2 |
| 42MKS4-1800G50-A4 | 42MKS4 district cooling | 4 | 50 | 1708/1396/1204 | 13.09 | 150 × 34 × 61.2 |
| 42MKS4-2000G50-A4 | 42MKS4 district cooling | 4 | 50 | 1907/1586/1337 | 14.15 | 150 × 34 × 61.2 |
| 42MKT4-400G30 | 42MKT4 4-row (7/12) | 4 | 30 | 400/300/200 | 3.43 | 91.2 × 24.1 × 50.6 |
| 42MKT4-600G30 | 42MKT4 4-row (7/12) | 4 | 30 | 600/450/300 | 5.4 | 113.5 × 24.1 × 50.6 |
| 42MKT4-800G30 | 42MKT4 4-row (7/12) | 4 | 30 | 800/600/400 | 6.61 | 143.5 × 24.1 × 50.6 |
| 42MKT4-1000G30 | 42MKT4 4-row (7/12) | 4 | 30 | 1000/750/500 | 8.09 | 154 × 24.1 × 50.6 |
| 42MKT4-1200G30 | 42MKT4 4-row (7/12) | 4 | 30 | 1200/900/600 | 9.74 | 183 × 24.1 × 50.6 |
| 42MKT4H-1600G100 | High static G100 | 4 | 100 | 1600 nominal | — | — |
| 42MKT4H-1800G100 | High static G100 | 4 | 100 | 1800 nominal | — | — |
| 42MKT4H-2200G100 | High static G100 | 4 | 100 | 2200 nominal | — | — |
| 42MKT3H-1600G100 | High static G100 | 3 | 100 | 1600 nominal | — | — |
| 42MKT3H-1800G100 | High static G100 | 3 | 100 | 1800 nominal | — | — |
| 42MKT3H-2200G100 | High static G100 | 3 | 100 | 2200 nominal | — | — |
Rating conditions: 42MKT3 and 42MKT4 at 7 °C entering / 12 °C leaving water and 27 °C DB / 19 °C WB air; 42MKS4 at 5.5 / 14.5 °C water and 27 °C DB / 19 °C WB air (600 Plus at 24 °C DB / 18 °C WB). All units 220–240 V single phase, three speeds, two-pipe, 16 bar maximum water pressure, RC ¾" water connections.
What we need for a correct selection
- Load schedule per space — total and sensible load and its source (HAP, manual calculation or the mall template).
- Entering and leaving water temperatures — 7/12, 5.5/14.5 or the project's own pair; the same model delivers a different capacity on each.
- External static pressure required — from duct length, number of grilles and filters (30, 50 or 100 Pa).
- Ceiling void height — below 30 cm above the false ceiling the 24.3 cm slim range is the answer.
- Control valve type — PICV, two-way or three-way, from the project or mall requirements.
- Fresh air quantity and source, connection hand (right as standard, left on request) and electric heater option, and BMS integration.
What our technical proposal includes
| Section | Content |
|---|---|
| Design basis | Project, shop, area, water temperatures, connection type, cooling load and its source, design revision |
| Proposed equipment | Each model with its catalogue photo and key data: rows, tubes, ESP, capacity, airflow, dimensions, weight |
| Engineering checks | Water ΔT, network pressure drop against the available head, water velocity, control valve, load consistency — compliant / review flags |
| Connection detail | Supply and return line per unit: isolation valves, flushing bypass, strainer, test points, flexible hoses, dielectric coupling, air vent |
| Controls | Thermostat per unit or zone with a valve output, ready for BMS integration |
| Network results | Total flow, critical path and pressure drop per segment — with the chilled-water network report as an annex |
| Exclusions and financial offer | Tie-in point, BTU meter, power supply and permits named explicitly; then items and quantities |
For procurement teams
- Vendor registration documents ready: commercial register, tax card, VAT certificate.
- Tax invoices for companies.
- Payment by bank transfer, cheque, cash or instalments against delivery milestones.
- Projects served across Egypt; supply from the agent's stores or El Shora's warehouse in 6th of October City.
Frequently asked questions
Are these fan coil units made in Egypt?
Yes. The 42MKT3, 42MKS4 and 42MKT4 ranges are manufactured in Egypt by Miraco, Carrier's Egyptian manufacturer, and El Shora works from the manufacturer's technical catalogues.
What is the difference between the 42MKT3, 42MKS4 and 42MKT4 series?
42MKT3 (Aqua Slim) is 24.3 cm high with a 3-row coil and 50 Pa external static pressure, rated at 7/12 °C water. 42MKS4 has a 4-row coil and its catalogue capacities are rated at 5.5/14.5 °C water, as district-cooling networks in malls require. 42MKT4 has a 4-row coil at 7/12 °C and 30 Pa for higher loads with short duct runs.
What do G30, G50 and G100 mean in the model code?
The external static pressure in pascals available for ducts and grilles: 30 Pa for short runs, 50 Pa as the standard for a ducted room, and 100 Pa (42MKT3H / 42MKT4H, 1,600–2,200 CFM) for long duct runs with several outlets or extra filters.
Can you supply only, without installation?
Yes. Supply-only to contractors against a purchase order, or supply, installation and commissioning together with the chilled-water piping, ducts and grilles in one bill of quantities.
How much does a fan coil unit cost?
No prices are published for fan coil units: the model itself is only fixed after the load schedule, the water temperatures and the external static pressure are known. Send these and you receive a written technical and financial proposal.
What does your technical proposal include?
Design basis, the proposed units with catalogue photo and key data, an engineering check table (water ΔT, network pressure drop against the available head, water velocity, control valve type, load consistency), the typical connection detail per unit, controls, chilled-water network results and named exclusions — in Arabic or English.
Can you register as a vendor and issue tax invoices?
Yes. Commercial register, tax card and VAT certificate are ready for vendor registration; tax invoices are issued for companies. Payment by bank transfer, cheque, cash or instalments against delivery milestones. Projects are served across Egypt.
Send us the load schedule
Load schedule, water temperatures and the external static pressure required. You receive a technical proposal with each model's photo and data and an engineering check table.